Defect register
Everything found on site and not yet rectified — ordered by severity so the dangerous work surfaces first.
Meridian Day Hospital
4 defects
| Severity | Reference | Defect | Site | Raised | Status |
|---|---|---|---|---|---|
| Critical | DF-4206Fault | Fire indicator panel showing permanent fault on Zone 4. Detection loop not reporting.FDA-00117 · Recovery Ward | Meridian Day HospitalHawthorn | 14 Jun 2026Nadia Fischer | Open |
| High | DF-4260Damage | Fire door will not self close — closer damaged and door binds on the frame.DOR-00125 · Sterilising Room | Meridian Day HospitalHawthorn | 21 May 2026Ben Kouassi | Open |
| Medium | DF-4275Fault | Emergency light failed to reach full duration — 62 minutes recorded against 90 required.EML-00122 · Sterilising Room | Meridian Day HospitalHawthorn | 11 Jul 2026Ben Kouassi | Open |
| Medium | DF-4272Wear | Hose reel rubber perished at the nozzle end. Replacement hose required at next service.FHR-00106 · Plant Room | Meridian Day HospitalHawthorn | 29 May 2026Tom Halloran | In progress |