Kestrel Distribution Centre

4 defects

SeverityReferenceDefectSiteRaisedStatus
MajorDF-4218DamageExit sign diffuser cracked and battery failed the 90 minute discharge test.EML-00206 · Warehouse Aisle 1Kestrel Distribution CentreLaverton North9 Aug 2026Nadia FischerIn progress
MajorDF-4269ObstructionAccess to two extinguishers blocked by stored pallets. Egress path narrowed.EXT-00183 · WorkshopKestrel Distribution CentreLaverton North22 Jul 2026Ben KouassiOpen
Non CriticalDF-4290WearSprinkler head lightly loaded with dust in the packing hall. Clean at next attendance.SPR-00195 · Battery Charging BayKestrel Distribution CentreLaverton North3 Aug 2026Nadia FischerOpen
MinorDF-4236WearSurface corrosion on the hydrant landing valve. Monitor and treat at the yearly service.HYD-00194 · Despatch OfficeKestrel Distribution CentreLaverton North10 Aug 2026Ben KouassiOpen