← Service diaryClosedSite record
All defects
MP-26014 · Meridian Day Hospital
Defect Rectification · 215 Burwood Road, Hawthorn VIC 3122
Attendance
Rectification of defects raised at the last routine service.
- Scheduled
- Sun 26 Jul
- 10am – 12pm
- On site
- 10:12am
- Off site 12:08pm
- Technician
- Ben Kouassi
- Client
- Meridian Health Services
- Grace Oyelaran
- Site contact
- 03 9330 5514
- Purchase order
- —
Scope on site
Systems the technician attends on this visit, with what is falling due
| System | Standard | Assets | Due |
|---|---|---|---|
| Emergency & Exit Lighting | AS 2293.2-2019 | 6 | 6 |
| Fire & Smoke Doors | AS 1851-2012 Section 17 | 9 | 8 |
| Fire Detection & Alarm | AS 1851-2012 Section 6 | 3 | 2 |
| Fire Hose Reels | AS 1851-2012 Section 11 | 13 | 9 |
| Portable Fire Extinguishers | AS 1851-2012 Section 10 | 10 | 7 |
Open defects at this site
Rectification the technician should carry to this visit
- CriticalFire indicator panel showing permanent fault on Zone 4. Detection loop not reporting.FDA-00117 · Recovery Ward · raised 14 Jun 2026
- HighFire door will not self close — closer damaged and door binds on the frame.DOR-00125 · Sterilising Room · raised 21 May 2026
- MediumEmergency light failed to reach full duration — 62 minutes recorded against 90 required.EML-00122 · Sterilising Room · raised 11 Jul 2026
- MediumHose reel rubber perished at the nozzle end. Replacement hose required at next service.FHR-00106 · Plant Room · raised 29 May 2026